The psychrometric calculator will assist you in estimating the properties of moist air. We can define humid or moist air conditions using temperature and pressure parameters such as wet-bulb temperature, dry-bulb temperature, and dew-point temperature. For pressure, we use the atmospheric pressure, the partial pressure of water vapor, and the saturated vapor pressure. The specific humidity and relative humidity are also useful to convey the condition of the air. The equations used here follow the guidelines issued by ASHRAE (the American Society of Heating, Refrigerating and Air-Conditioning Engineers), which are critical in heating, ventilation, and air-conditioning (HVAC) applications.
What is dry-bulb temperature? What is wet-bulb temperature?
Psychrometry is the science that covers the conditions of humid or moist air. Its principles are the lynchpin in designing industrial and residential applications: ventilation of large buildings, mixing air streams in air conditioning, industrial drying, and human comfort. The atmosphere is a mixture of dry air and water vapor, often known as moist air. Its condition is defined by a set of parameters:
- Dry-bulb temperature (Tdb);
- Wet-bulb temperature (Twb);
- Dew-point temperature (Tdp);
- Atmospheric pressure (Pa);
- Partial vapor pressure (Pv);
- Saturated vapor pressure (Ps);
- Relative humidity (Φ); and
- Specific humidity (ω).
Wet-bulb temperature is the lowest temperature to which air can be cooled by evaporating water into it at constant pressure. To measure it, you wrap a wet wick around the bulb of a thermometer — the reading it shows is the wet-bulb temperature.
Dry-bulb temperature is the temperature measured by a thermometer at ambient pressure, i.e., the ambient air temperature. The difference between the dry-bulb and wet-bulb temperatures indicates the humidity of the air: the smaller the difference, the more humid the air.
Dew-point temperature is the temperature below which water vapor in the air condenses into the liquid state. For a given vapor pressure Pv:
Tdp = 243.5·ln(Pv/6.112) / (17.67 − ln(Pv/6.112))
Types of humidity — How to calculate specific humidity?
The saturated vapor pressure Ps is the maximum partial pressure of water vapor for a given temperature — the point at which the air is saturated. It is computed with the Magnus equation:
Ps = 6.112·e(17.67·T / (T + 243.5)) [hPa], with T in °C.
The relative humidity Φ is the ratio of the actual vapor pressure to the saturation pressure: Φ = Pv / Ps × 100%. The specific humidity (humidity ratio) ω is the mass of water vapor per unit mass of dry air:
ω = 0.62198 · Pv / (P − Pv)
Specific volume and enthalpy
The specific volume of moist air is the volume occupied per unit mass of dry air, and the enthalpy is its total heat content per unit mass of dry air:
- v = Ra·T·(1 + 1.6078·ω) / P [m³/kg dry air]
- h = 1.006·T + ω·(2501 + 1.86·T) [kJ/kg dry air]
How to use the psychrometric calculator
- Choose your unit system — Metric (SI) or Imperial (US).
- Enter the dry-bulb temperature.
- Select the second known parameter: relative humidity, wet-bulb temperature, or dew-point temperature, and enter its value.
- Enter the atmospheric pressure (default is the standard sea-level pressure, 1013.25 hPa / 29.92 inHg).
- Press Calculate to obtain the full set of moist-air properties.
Example: Using the psychrometric calculator
Suppose the dry-bulb temperature is 25 °C, the relative humidity is 50%, and the atmospheric pressure is 1013.25 hPa. The calculator returns a wet-bulb temperature of about 18.0 °C, a dew point of about 13.9 °C, a humidity ratio of roughly 9.9 g/kg, a specific volume near 0.858 m³/kg, and an enthalpy of about 50.4 kJ/kg of dry air.
ASHRAE Psychrometric chart — How to find relative humidity using psychrometric charts?
A psychrometric chart plots dry-bulb temperature on the horizontal axis and humidity ratio on the vertical axis, with curved lines of constant relative humidity, wet-bulb temperature, and enthalpy. To find the relative humidity graphically: locate the dry-bulb temperature on the bottom axis, move up to the point that matches your wet-bulb or dew-point line, and read the relative-humidity curve passing through that point. This calculator performs the same lookup numerically using the ASHRAE equations.
FAQs
- What is the difference between dry-bulb and wet-bulb temperature?
- Dry-bulb temperature is the ordinary air temperature. Wet-bulb temperature is always equal to or lower than the dry-bulb temperature and reflects evaporative cooling. They are equal only at 100% relative humidity.
- What is specific humidity?
- The mass of water vapor present per unit mass of air. The closely related humidity ratio (ω) expresses it per unit mass of dry air.
- Does atmospheric pressure affect the result?
- Yes. Pressure changes the humidity ratio, specific volume, and the relationship between wet-bulb and dew-point temperatures, so altitude (lower pressure) shifts the moist-air properties.
- What is the standard atmospheric pressure?
- At mean sea level it is 101325 Pa (1013.25 hPa, 1.013 bar, or 29.92 inHg).